Technical parameters
Overview
With the rapid development of China's national economy, electricity and lighting demands of subways, airports, tunnels, bridges and buildings that are building in all major large and medium-sized cities all have an urgent need: power transmission and distribution lines that both comply with environmental protection requirements and can adapt to the characteristics of the above-mentions buildings.。
To meet market demand, Shanghai SOCO Group New Product Research Institute has specially developed large-section armored multi-core prefabricated branch cables in line with the environmental requirements, which have been put into mass production. The type and specification includes: Common type, cross-linked, flame-retardant, fire-retardant, safe and clean type, oxygen barrier flame-retardant and fire-retardant. Maximum cross section of the cable up to 240mm2/phase; branch sections can be produced according to user requirements.
Armored multi-core branch cable type demonstration
Armored multi-core safe and clean (environmentally-friendly) branch cable type demonstration
VV PVC insulated PVC 4-core power cable parameters (0.6/1kv)
Conductor nominal cross-sectional area (mm2) |
Insulation thickness (mm) |
Sheath thickness (mm) |
The approximate diameter (mm) |
The approximate weight (kg/km) |
20 ℃ maximum conductor resistance Ω/km |
Rated current A. |
Voltage drop (mV/m) |
|
In the air of 40 ℃ | In the air of 30 ℃ | |||||||
4×10 4×16 |
1.0 1.0 |
1.8 1.8 |
18.6 20.8 |
682 1010 |
1.83 1.15 |
52 70 |
60 80 |
84 69 |
4×25 4×35 |
1.2 1.2 |
1.8 1.9 |
24.7 27.1 |
1411 1835 |
0.727 0.524 |
88 110 |
101 126 |
56 50 |
4×50 4×70 |
1.4 1.4 |
1.9 2.2 |
28.2 32 |
2435 3271 |
0.387 0.268 |
133 170 |
153 196 |
45 39 |
4×95 4×120 |
1.6 1.6 |
2.3 2.5 |
36.7 43 |
4338 5383 |
0.193 0.153 |
207 240 |
238 276 |
36 32 |
4×150 4×185 |
1.8 2.0 |
2.6 2.8 |
47.7 52.7 |
6712 8207 |
0.124 0.0991 |
277 316 |
319 364 |
30 28 |
4×240 4×300 |
2.2 2.4 |
3.0 3.2 |
59.4 65.2 |
10850 13647 |
0.0754 0.0601 |
374 432 |
430 497 |
25 23 |
VV PVC insulated PVC 4+1-core power cable parameters (0.6/1kv)
Conductor nominal cross-sectional area (mm2) |
Insulation thickness (mm) |
Sheath thickness (mm) |
The approximate diameter (mm) |
The approximate weight (kg/km) |
20 ℃ maximum conductor resistance Ω/km |
Rated current A. |
Voltage drop (mV/m) |
|
In the air of 40 ℃ | In the air of 30 ℃ | |||||||
4×10+1×6 4×16+1×10 |
1.0 1.0 |
1.8 1.9 |
18 20.7 |
720 1055 |
1.83 1.15 |
52 70 |
60 80 |
84 69 |
4×25+1×16 4×35+1×16 |
1.2 1.2 |
1.9 1.9 |
24.6 26.8 |
1578 1988 |
0.727 0.524 |
88 110 |
101 126 |
56 50 |
4×50+1×25 4×70+1×35 |
1.4 1.4 |
2.1 2.2 |
28.5 30.6 |
2683 3609 |
0.387 0.268 |
133 170 |
153 196 |
45 39 |
4×95+1×50 4×120+1×70 |
1.6 1.6 |
2.4 2.5 |
34.7 38.1 |
4836 6055 |
0.193 0.153 |
207 240 |
238 276 |
36 32 |
4×150+1×70 4×185+1×95 |
1.8 2.0 |
2.7 2.9 |
42.6 47.4 |
7384 8911 |
0.124 0.0991 |
277 316 |
319 364 |
30 28 |
4×240+1×120 | 2.2 | 3.1 | 53.2 | 11414 | 0.0754 | 374 | 430 | 25 |
YJV XLPE insulated PVC sheathed 3 + 1-core power cable parameters (0.6/1kv)
Conductor nominal cross-sectional area (mm2) |
Insulation thickness (mm) |
Sheath thickness (mm) |
The approximate diameter (mm) |
The approximate weight (kg/km) |
20 ℃ maximum conductor resistance Ω/km |
Rated current A. |
Voltage drop (mV/m) |
|
In the air of 40 ℃ |
In the air of 30 ℃ | |||||||
3×10+1×6 3×16+1×10 |
0.7/0.7 0.7/0.7 |
1.8 1.8 |
16.4 18.5 |
503 727 |
1.83 1.15 |
68 91 |
75 100 |
84 69 |
3×25+1×16 3×35+1×16 |
0.9/0.7 0.9/0.7 |
1.8 1.8 |
22.3 24.8 |
1092 1476 |
0.727 0.524 |
116 144 |
127 158 |
56 50 |
3×50+1×25 3×70+1×35 |
1.0/0.9 1.1/0.9 |
1.8 1.9 |
25.9 29.9 |
1907 2612 |
0.387 0.268 |
174 224 |
192 246 |
45 39 |
3×95+1×50 3×120+1×70 |
1.1/1.0 1.2/1.1 |
2.1 2.2 |
33.7 37.5 |
3489 4448 |
0.193 0.153 |
271 315 |
298 346 |
36 32 |
3×150+1×70 3×185+1×95 |
1.4/1.1 1.6/1.1 |
2.3 2.5 |
41.6 46.7 |
5383 6711 |
0.124 0.0991 |
363 415 |
399 456 |
30 28 |
3×240+1×120 3×300+1×150 |
1.7/1.2 1.8/1.4 |
2.7 2.9 |
51.9 57 |
8561 11080 |
0.0754 0.0601 |
490 565 |
538 620 |
25 23 |
YJV XLPE insulated PVC sheathed 4-core power cable parameters (0.6/1kv)
Conductor nominal cross-sectional area (mm2) |
Insulation thickness (mm) |
Sheath thickness (mm) |
The approximate diameter (mm) |
The approximate weight (kg/km) |
20 ℃ maximum conductor resistance Ω/km |
Rated current A. |
Voltage drop (mV/m) |
|
In the air of 40 ℃ | In the air of 30 ℃ | |||||||
4×10 4×16 4×25 |
0.7 0.7 0.9 |
1.8 1.8 1.8 |
18.6 20 20 |
610 879 1286 |
1.83 1.15 0.727 |
68 91 116 |
75 100 127 |
84 69 56 |
4×35 4×50 |
0.9 1.0 |
1.9 1.9 |
26 28 |
1688 2341 |
0.524 0.387 |
144 174 |
158 192 |
50 45 |
4×70 4×95 |
1.1 1.1 |
2.2 2.3 |
33 36 |
3175 4171 |
0.268 0.193 |
224 271 |
246 298 |
39 36 |
4×120 4×150 |
1.2 1.4 |
2.5 2.6 |
37 39.5 |
5262 6542 |
0.153 0.124 |
315 363 |
346 399 |
32 30 |
4×185 4×240 |
1.6 1.7 |
2.8 3.0 |
45 54 |
7893 10215 |
0.0991 0.0754 |
415 490 |
456 538 |
28 25 |
4×300 | 1.8 | 3.2 | 58 | 11643 | 0.0601 | 565 | 620 | 23 |
YJV XLPE insulated PVC sheathed 4 + 1-core power cable parameters (0.6/1kv)
Conductor nominal cross-sectional area (mm2) |
Insulation thickness (mm) |
Sheath thickness (mm) |
The approximate diameter (mm) |
The approximate weight (kg/km) |
20 ℃ maximum conductor resistance Ω/km |
Rated current A. |
Voltage drop (mV/m) |
|
In the air of 40 ℃ | In the air of 30 ℃ | |||||||
4×10+1×6 4×16+1×10 |
0.7 0.7 |
1.8 1.8 |
18 20.7 |
619 911 |
1.83 1.15 |
68 91 |
75 100 |
84 69 |
4×25+1×16 4×35+1×16 |
0.9 0.9 |
1.8 1.8 |
24.6 26.8 |
1359 1749 |
0.727 0.524 |
116 144 |
127 158 |
56 50 |
4×50+1×25 4×70+1×35 |
1.0 1.1 |
1.9 2.0 |
28.5 30.6 |
2387 3280 |
0.387 0.268 |
174 224 |
192 246 |
45 39 |
4×95+1×50 4×120+1×70 |
1.1 1.2 |
2.2 2.4 |
34.7 38.1 |
4407 5580 |
0.193 0.153 |
271 315 |
298 346 |
36 32 |
4×150+1×70 4×185+1×95 |
1.4 1.6 |
2.5 2.6 |
42.6 47.4 |
6803 8158 |
0.124 0.0991 |
363 415 |
399 456 |
30 28 |
4×240+1×120 | 1.7 | 2.8 | 53.2 | 10850 | 0.0754 | 490 | 538 | 25 |
Steel tape-armored multi-core power cable parameters (0.6/1KV)
Conductor nominal cross-sectional area (mm2) |
The approximate diameter(mm) | The approximate weight (kg/km) | ||||||||||||||
VV22 | YJV22 | VV22 | YJV22 | |||||||||||||
3+1-core | 4-core | 4+1-core | 5-core | 3+1-core | 4-core | 4+1-core | 5-core | 3+1-core | 4-core | 4+1-core | 5-core | 3+1-core | 4-core | 4+1-core | 5-core | |
4 6 |
17.9 19.5 |
18.5 19.7 |
19.2 20.8 |
19.7 21.3 |
16 17 |
17 17 |
17 18 |
17 19 |
538 657 |
565 685 |
605 765 |
644 790 |
425 527 |
445 550 |
485 637 |
507 638 |
10 16 |
22.1 24.7 |
22.8 25.3 |
23.9 26.9 |
24.6 27.4 |
20 23 |
20 23 |
21 24 |
22 25 |
894 1194 |
960 1273 |
1052 1482 |
1110 1485 |
734 1019 |
787 1076 |
882 1208 |
926 1277 |
25 35 |
28.5 31.7 |
30.5 33.5 |
32.4 35.1 |
33.3 36.6 |
26 28 |
27 29 |
28 30 |
28 33 |
1668 2243 |
1998 2505 |
2312 2756 |
2339 2953 |
1434 1757 |
1519 1957 |
1713 2152 |
1817 2705 |
50 70 |
35 38.5 |
35.2 38.7 |
39.7 44 |
41.6 45.5 |
31 36 |
33 38 |
36 41 |
37 42 |
2852 3657 |
3122 4025 |
3680 4768 |
3975 5125 |
2229 3386 |
2759 3678 |
3263 4376 |
3525 4732 |
95 120 |
44.3 49 |
44.7 49.4 |
50.2 55.1 |
52.1 57.3 |
40 44 |
42 47 |
46 51 |
48 53 |
4796 5912 |
5291 6464 |
6267 7689 |
6798 8217 |
4397 5468 |
4832 5906 |
5695 7129 |
6256 7571 |
150 185 |
53.5 58.9 |
53.7 58.9 |
59.9 66.5 |
63.1 69.9 |
49 52 |
52 56 |
55 61 |
58 65 |
7025 8598 |
7866 9542 |
9216 11293 |
10030 12275 |
6464 8004 |
7186 8807 |
8282 10287 |
9221 11319 |
240 300 |
60.6 65.6 |
61 66.2 |
74 81.9 |
77.1 86.5 |
58 63 |
62 68 |
69 76 |
73 80 |
10631 12913 |
11916 14501 |
14371 17385 |
15077 19395 |
10140 12445 |
11268 13824 |
13163 16169 |
14631 17948 |
Note: The remaining parameters are same that of similar power cables (VV, YJV), and power cables with same sections or same number of cores.
Description: Rated currents of VV and YJV type cables are the data when laying in the following standards.
(1) VV plastic insulation
a. Maximum working temperature of conductor = 70 ℃ b
b. Ambient air temperature =40 ℃
c. Ground temperature is over 25 ℃
d. Soil thermal resistance =1.0Km / W
e. Underground laying depth= 0.5m
(2) YJV insulation
a、Maximum working temperature of conductor = 90 ℃ b
b、Ambient air temperature =40 ℃
c、Ground temperature is over 25 ℃
d、Soil thermal resistance =1.0Km / W
e、 Underground laying depth= 0.5m