Polyvinyl Chloride Insulated Sheathed Power Cable
Product classification
Keywords
- Product Description
-
Purpose
This product is suitable for AC 50Hz, rated voltage 0.6/1kV lines, for the purpose of power transmission and distribution.
Usage Characteristics
1) The maximum rated temperature of the cable conductor is 70℃.
2) During a short circuit, (the maximum duration does not exceed 5s) the maximum temperature of the cable conductor does not exceed 160℃.
3) The ambient temperature when laying the cable should not be lower than 0℃, and the minimum bending radius should not be less than 10 times the outer diameter of the cable.
Model and NameModel
Name
Applicable Scope
VV
VLVPVC insulated PVC sheathed power cable
Laid indoors, in tunnels and pipes, the cable cannot withstand pressure and mechanical external forces.
VV22
VLV22PVC insulated steel tape armored PVC sheathed power cable
Laid indoors, in tunnels and directly buried in soil, the cable can withstand pressure and other external forces.
VV32
VLV32PVC insulated fine steel wire armored PVC sheathed power cable
Laid indoors, in mines, underwater, the cable can withstand considerable tensile force.
VV42
VLV42PVC insulated coarse steel wire armored PVC sheathed power cable
Laid in vertical situations such as shafts and underwater, can withstand considerable axial tensile force.
ZR-VV
ZR-VLVPVC insulated PVC sheathed flame-retardant power cable
Laid indoors, in tunnels and pipes, the cable cannot withstand pressure and mechanical external forces.
ZR-VV22
ZR-VLV22PVC insulated steel tape armored PVC sheathed flame-retardant power cable
Laid indoors, in tunnels and directly buried in soil, the cable can withstand pressure and other external forces.
ZR-VV32
ZR-VLV32PVC insulated fine steel wire armored PVC sheathed flame-retardant power cable
Laid indoors, in mines, underwater, the cable can withstand considerable tensile force.
ZR-VV42
ZR-VLV42PVC insulated coarse steel wire armored PVC sheathed flame-retardant power cable
Laid in vertical situations such as shafts and underwater, can withstand considerable axial tensile force.
Structural Dimensions, Technical ParametersWire Nominal
Cross-section
mm2In the conductor
Number of single wiresInsulation
Thickness
mmSheath Thickness
mmApproximate
Outer Diameter
mmApproximate Weight of Cable
DC Resistance of Wire
Test Voltage
(kV/5min)kg/km
kg/km
Ω/km
Ω/km
Cu
Al
20℃ Cu
20℃ Al
1×1.5
1
0.8
1.4
6.1
50.7
41.3
12.1
-
3.5
1×2.5
1
0.8
1.4
6.5
63.5
47.9
7.41
12.1
3.5
1×4
1
1.0
1.4
7.4
87.7
63.0
4.61
7.41
3.5
1×6
1
1.0
1.4
7.9
111.0
75.9
3.08
4.61
3.5
1×10
7
1.0
1.4
9.2
166.6
93.0
1.83
3.02
3.5
1×16
7
1.0
1.4
10.3
233.3
132.2
1.15
1.91
3.5
1×25
7
1.2
1.4
12.0
344.9
185.4
0.727
1.20
3.5
1×35
7
1.2
1.4
13.2
449.8
228.7
0.524
0.868
3.5
1×50
19
1.4
1.4
14.9
590.5
289.8
0.387
0.641
3.5
1×70
19
1.4
1.4
16.7
807.3
374.2
0.268
0.443
3.5
1×95
19
1.6
1.5
19.3
1102.0
501.4
0.193
0.320
3.5
1×120
37
1.6
1.5
20.9
1349.0
590.3
0.153
0.253
3.5
1×150
37
1.8
1.6
23.1
1654.0
721.3
0.124
0.206
3.5
1×185
37
2.0
1.7
25.6
2060.0
891.6
0.0991
0.164
3.5
1×240
61
2.2
1.8
28.8
2651.0
1114.0
0.0754
0.125
3.5
1×300
61
2.4
1.9
31.9
3323.0
1396.0
0.0601
0.100
3.5
1×400
61
2.6
2.0
35.5
4205.0
1742.0
0.0470
0.0778
3.5
1×500
61
2.8
2.1
39.7
5359.0
2128.0
0.0366
0.0605
3.5
1×630
91
2.9
2.2
43.7
6707.0
2605.0
0.0283
0.0469
3.5
1×800
61
2.9
2.4
46.1
8064.0
3104.0
0.0221
0.0367
3.5
Polyvinyl Chloride Insulated Sheathed Power Cable